A joint or termination is matched to one cable, so the specification must state the conductor, cross-section, insulation, screen, rated voltage U0/U (Um), core count and indoor or outdoor use, plus the type-test standard: IEC 60502-4, HD 629.1, IEEE 48 or IEEE 404. EUROMEXA supplies the kits against your bill of quantities, with the manufacturer's type-test evidence named in the quotation. Quotation within 24–72 hours.
EUROMEXA is an independent supplier, not an authorised distributor or affiliate of any manufacturer named here; brand names identify compatibility only.
What the specification must state
| Item | Why it matters |
|---|---|
| Rated voltage U0/U (Um) of the cable | Sizes the insulation and stress control of the accessory; 33 kV networks usually call for a 36 kV (Um) class |
| Conductor material and cross-section (mm² or kcmil) | Sets the connector or lug and the size range of the kit |
| Insulation type (XLPE, EPR) and diameter over insulation | Each kit covers a diameter range; outside it, it will not seal or control stress |
| Screen type (copper wire, tape, lead or aluminium sheath) and armour | Decides the earthing and screen-continuity parts of the kit |
| Single-core or three-core cable | Three-core joints and terminations use a different kit (with a breakout for terminations) |
| Joint, termination or both; indoor or outdoor; creepage or pollution level for outdoor | Outdoor terminations need sheds and creepage for the site |
| What the termination connects to (switchgear bushing, transformer, overhead line) | Decides between a standard lug termination and a separable connector |
| Quantity per type, spares and installation tools if required | Each kit is quoted as a complete line |
Which type-test standard does the tender name?
Accessories are type-tested as a design: the manufacturer's type-test report shows that the design passed the sequence of a standard. The tender should name that standard; the four below are the usual ones.
- The IEC titles state "up to 30 kV (Um = 36 kV)"; they do not use the words 33 kV. Confirm the cable's U0/U (Um) against the range of the standard the tender names.
- If a voltage falls outside the named standard's range, ask in writing which standard applies before quoting.
| Standard | Scope (as published by the standards body) |
|---|---|
| IEC 60502-4:2023 | Type tests for accessories on extruded-insulation cables from 3,6/6 (7,2) kV up to 18/30 (36) kV, cables to IEC 60502-2 |
| CENELEC HD 629.1 S3:2019 | Joints, terminations, stop ends and separable connectors for extruded-insulation cables from 3,6/6(7,2) kV up to 20,8/36(42) kV |
| IEEE 48-2020 | AC cable terminations on shielded cables, extruded insulation rated 2.5 kV through 500 kV |
| IEEE 404-2022 | Joints for extruded and laminated dielectric shielded cables rated 2.5 kV to 500 kV |
Heat-shrink, cold-shrink or push-on?
All three technologies exist for medium-voltage joints and terminations. The tender, the utility's practice and the installers' training usually decide: heat-shrink needs a torch and controlled heating; cold-shrink and push-on parts are fitted without heat. Whatever the technology, the type-test report must cover the design offered.
Documents named in the quotation
- The manufacturer's type-test report to the standard the tender names, for the design offered
- Datasheet and installation instructions for each kit
- Routine or sample test records where the specification asks for them
- Commercial invoice, packing list and certificate of origin where applicable, from EUROMEXA
- EUROMEXA does not type-test or certify accessories: the test evidence is the manufacturer's
How EUROMEXA quotes the package
- Line by line against your bill of quantities, with the kit range checked against the cable data
- One quotation from EUROMEXA: price, lead time, Incoterm and the standard each line meets
- Questions on the cable data or the standard go back to you in writing before the quotation
- Payment: first orders are paid in advance or with a deposit; credit terms are available for established accounts
Questions and answers
- Which standard covers 33 kV cable joints and terminations?
- The tender names it. IEC 60502-4 covers accessories for cables up to 18/30 (36) kV; HD 629.1 goes up to 20,8/36 (42) kV; IEEE 48 covers terminations and IEEE 404 covers joints.
- What cable data do I need to send?
- Rated voltage U0/U (Um), conductor material and cross-section, insulation type and diameter, screen and armour, single- or three-core, and whether each item is a joint or an indoor or outdoor termination.
- Can one kit fit any 33 kV cable?
- No. Each kit covers a range of conductor sizes and insulation diameters for one cable construction.
- Does EUROMEXA type-test the kits?
- No. Type-test reports come from the manufacturer for the design offered; the quotation names them per line.
- Can EUROMEXA quote the whole bill of quantities?
- EUROMEXA reads the full list and confirms line by line what it can supply, in one quotation, within 24–72 hours.
Sources
- IEC (International Electrotechnical Commission): IEC 60502-4:2023 — Test requirements on accessories for cables with rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV) (Third party; checked 2026-11-17)
- IEC (International Electrotechnical Commission): IEC 60502-2 — Power cables with extruded insulation, Part 2: cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV) (Third party; checked 2026-11-17)
- BSI (British Standards Institution): BS HD 629.1 S3:2019 — Test requirements for accessories for power cables from 3,6/6(7,2) kV up to 20,8/36(42) kV, extruded insulation (Third party; checked 2026-11-17)
- IEEE Standards Association: IEEE 48-2020 — Test procedures and requirements for AC cable terminations, 2.5 kV through 765 kV (laminated) / 500 kV (extruded) (Third party; checked 2026-11-17)
- IEEE Standards Association: IEEE 404-2022 — Extruded and laminated dielectric shielded cable joints rated 2.5 kV to 500 kV (Third party; checked 2026-11-17)
Last checked 2026-11-17.